Heat meters SARBAZ-TS are designed for measuring, calculating, displaying, and recording, within heating supply and hot water systems as well as cooling (air-conditioning) systems, the values of consumed (delivered) heat energy, volume, mass, temperatures, pressures, and other parameters of the heat-transfer medium.
The heat meters are used for automating metering, telemetry control, and organizing information networks for data collection using wired and wireless communication channels.
Scope of application: enterprises of heat networks, heating units of residential, public, and industrial buildings, central heating units, heat sources, heat networks and cooling (air-conditioning) systems of industrial and domestic facilities (buildings), residential single-family houses and apartments.
|
Characteristics |
Value |
|
1 |
2 |
|
Heat-transfer medium |
water |
|
Working pressure, MPa, not more than |
1.6 or 2.5 |
|
Heat-transfer medium flow measurement range, m³/h |
0.015 - 200.0 |
|
Heat-transfer medium temperature measurement range, °C |
from 0 to 150 |
|
Heat-transfer medium temperature difference measurement range, °C |
from 2 to 150 |
|
Measurement range of input analog signals proportional to excess pressure, mA |
from 4 to 20 |
|
Accuracy class according to ST RK 2.105 (ST RK GOST R EN 1434-1) |
B (2) C(1) |
|
Limits of permissible relative error of the heat quantity measuring channel according to ST RK 2.105, % - class B - class C |
±(3 + 4Δtₕ/Δt + 0.02Gᵦ/G) where G and Gₑ are the flow rate values of the heat-transfer medium and its maximum value in the supply pipeline, m³/h; Δtₕ/Δt is the temperature difference in the supply and return pipelines of the heat-exchange circuit, °C. |
|
Limits of permissible relative error when measuring mass and volume flow rate, mass, and volume of the heat-transfer medium according to ST RK GOST R EN 1434-1-2010, % - for class (2) - for class (1)1) |
±(2.0 + 0.02qₚ/q), but not more than ±5.0; qₚ – constant flow rate (maximum flow rate at which the heat meter operates continuously without exceeding the maximum permissible error), m³/h; |
|
Limits of permissible absolute error of the calculator when converting signals from resistance temperature detectors, °C |
±(0.1 + 0.00014) |
|
Limits of permissible absolute error in temperature measurement, °C: – with Class A resistance temperature detectors according to GOST 6651-2009 – with Class B resistance temperature detectors according to GOST 6651-2009 |
±(0.25+0.00214) ±(0.4 + 0.00514) |
|
Maximum permissible temperature sensor error (ST RK GOST R EN 1434-1-2010), % |
± (0.5 + Δtₘᵢₙ/Δt) Δtₘᵢₙ – minimum temperature difference, °C; |
|
Maximum permissible calculator error (ST RK GOST R EN 1434-1-2010), % |
± (0.5 + Δtₘᵢₙ/Δt) Δtₘᵢₙ – minimum temperature difference, °C; |
|
Limits of permissible reduced error of the calculator when converting excess pressure sensor signals, % |
±0.15 |
|
Limits of permissible reduced error of excess pressure sensors, % |
±1.85 |
|
Limits of permissible relative error of the heat meter when measuring excess pressure, % |
±2.0 |
|
Limits of permissible relative error when measuring time intervals, % |
±0.01 |
|
Power supply from AC mains: - voltage, V - frequency, Hz |
from 187 to 253; from 49 to 51 |
|
Operating conditions: - ambient temperature, °C - relative air humidity at temperatures up to 30 °C, % - atmospheric pressure, kPa |
from +5 to +55; up to 95; from 84 to 106.7 |
|
Power consumption, VA, not more than |
30 |
|
Dimensions of the measuring and calculating unit, mm, not more than |
205x182x95 |
|
Weight of the measuring and calculating unit, kg, not more than |
2.0 |
|
Degree of protection provided by the enclosure, according to GOST 14254-2015 |
IP54 |
|
Mean time between failures, hours, not less than |
80,000 |
|
Average service life, years, not less than |
15 |
- Certificate of Approval of the Type of Measuring Instruments - Download
- Certificate of Origin of Goods - Download
- Description of the Measuring Instrument Type - Download
- EAEU Declaration of Conformity - Download
- Operating Manual - Download
- Communication Protocol Description - Download
- Technical Passport - Download
- Order Form for the Heat Meter SARBAZ-TS - Download